Home›Repair guides›Kohler›Procedure to Change the Service Disconnect Position Setting on the Controller

Kohler — Procedure to Change the Service Disconnect Position Setting on the Controller

Adjustments · Decision-Maker MPAC 1500 controller

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Use a USB cable to connect your laptop PC to the MPAC controller.
  2. Start SiteTech and wait for it to connect to the MPAC controller.
  3. Click on Set Mpac Password and enter the distributor password.
  4. Find the Service Disconnect Position setting in the ATS Connection Configuration group.
  5. Change the Service Disconnect Position setting to Source E.
  6. Apply changes to save the new setting.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.