Kohler — PowerBoost V Voltage Regulator Test Procedure (240 Volt A- or B-Board)

Testing & diagnosis · PowerBoost V voltage regulator 240 Volt A- or B-board

From a Kohler service manual covering: 4CFKM, 4CKM, 5CKM, 5CKM/SCKMR, ACKM/4CKMR. Check it applies to your exact model before use.

Applies to: Kohler 4CFKM, Kohler 4CKM, Kohler 5CKM, Kohler M18 engine, Kohler M20 engine

Before you start

  • Test regulator field for a maximum of one minute followed by a five-minute cooldown.

Procedure

  1. Connect components as shown in Figure 7-9.
  2. If plug is 250 volts use 250-volt lamp; if 120 volts use 120-volt lamp.
  3. Turn Volts potentiometer fully clockwise.
  4. Set variac to zero or minimum voltage and plug in.
  5. Slowly increase variac; lamp should illuminate at approximately 90 volts.
  6. Adjust variac to 240 volts; lamp should illuminate brightly.
  7. Turn Volts pot fully counterclockwise; lamp should go off.
  8. Turn power supply off and disconnect power cord.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Lamp illuminates at approximately 90 volts
  • Do not exceed 300 volts

Full service-parts list: Kohler 4CFKM →, Kohler 4CKM →, Kohler 5CKM →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.