Home›Repair guides›Kohler›PowerBoost V Voltage Regulator Adjustment Procedure

Kohler — PowerBoost V Voltage Regulator Adjustment Procedure

Adjustments

From a Kohler service manual covering: 4CFKM, 4CKM, 5CKM, 5CKM/SCKMR, ACKM/4CKMR. Check it applies to your exact model before use.

Applies to: Kohler 4CFKM, Kohler 4CKM, Kohler 5CKM, Kohler M18 engine, Kohler M20 engine

Before you start

  • Hazardous voltage. Moving rotor.

Procedure

  1. Turn voltage and volts/Hz pots fully counterclockwise.
  2. Start generator; rotate voltage adjustment pot to desired output voltage.
  3. Rotate stability pot clockwise until light flicker is minimized.
  4. Adjust engine speed to cut-in frequency (56.3 Hz / 46.3 Hz).
  5. Rotate volts/Hz pot clockwise until voltage begins to drop.
  6. Readjust engine speed to normal (1800 rpm / 1500 rpm).
  7. Readjust stability and voltage pots; stop generator set.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

Full service-parts list: Kohler 4CFKM →, Kohler 4CKM →, Kohler 5CKM →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →