Home›Repair guides›Kohler›PowerBoost IIIE Voltage Regulator Test Procedure

Kohler — PowerBoost IIIE Voltage Regulator Test Procedure

Testing & diagnosis

From a Kohler service manual covering: 4CFKM, 4CKM, 5CKM, 5CKM/SCKMR, ACKM/4CKMR. Check it applies to your exact model before use.

Applies to: Kohler 4CFKM, Kohler 4CKM, Kohler 5CKM, Kohler M18 engine, Kohler M20 engine

Before you start

  • Hazardous voltage. High voltage is present at the heat sink of the voltage regulator. Do not touch.

Procedure

  1. Disconnect P10 connector from voltage regulator.
  2. Connect components per Figure 7-5.
  3. Turn variable transformer to zero and plug in.
  4. Increase to 100 volts; if lamp off, turn voltage pot clockwise.
  5. If lamp still off, regulator is defective and should be replaced.
  6. Increase to 120 volts; lamp should go out.
  7. Turn variable transformer to zero and unplug.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Lamp should go out at 120 volts

Full service-parts list: Kohler 4CFKM →, Kohler 4CKM →, Kohler 5CKM →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →