Kohler — Oil Sentry Pressure Switch Testing

A Kohler service procedure — check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Connect continuity tester across blade terminal and metal case of switch. With 0 psi pressure applied to switch, tester should indicate continuity (switch closed).
  2. Gradually increase pressure to switch. As pressure increases through range of 3-5 psi tester should indicate a change to no continuity (switch open). Switch should remain open as pressure is increased to 90 psi maximum.
  3. Gradually decrease pressure through range of 3-5 psi. Tester should indicate a change to continuity (switch closed) down to 0 psi.
  4. Replace switch if it does not operate as specified.

Tools required

  • compressed air
  • pressure regulator
  • pressure gauge
  • continuity tester

Specs & torque values

  • 3-5 psi

Source: manual:sm_24_690_06.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.