For the Kohler MPAC 1500, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Will cause severe injury or death. Only authorized personnel should open the enclosure.
  • On service entrance transfer switches, the line side lugs are active at all times.
  • Controller power is not disconnected by the service disconnect procedure.

Procedure

  1. Move the service disconnect control switch on the transfer switch door to the SERVICE DISCONNECT position.
  2. The engine start contacts close, signaling the generator set to start.
  3. When the emergency source is available, the ATS transfers to the emergency source.
  4. Check that the utility breaker is open and the service disconnected pilot light is illuminated.
  5. Open the generator set circuit breaker, move the master switch to OFF/RESET, disconnect the battery charger, and remove battery cables (negative lead first).
  6. Use a voltmeter to verify that power is disconnected before servicing connected equipment.
  7. Attach a safety lockout padlock to the service disconnect control switch and verify the door is locked closed.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.