For the Kohler MPAC 1500, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Resetting to the default parameters resets all parameters including system voltage and frequency; the transfer switch will not operate correctly if they do not match the sources.
  • Disable the test password only during service unless the transfer switch is installed in a secure location.

Procedure

  1. Use the black arrow buttons to step to the desired reset screen.
  2. Press the open up arrow button to toggle Yes or No until Yes is displayed.
  3. Press Save to reset the displayed records to the factory defaults, or press Back to exit without resetting.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.