Kohler MPAC 1500 — Reset Data Procedure
Operation · MPAC 1500 controller
For the Kohler MPAC 1500, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Resetting to the default parameters resets all parameters including system voltage and frequency; the transfer switch will not operate correctly if they do not match the sources.
- Disable the test password only during service unless the transfer switch is installed in a secure location.
Procedure
- Use the black arrow buttons to step to the desired reset screen.
- Press the open up arrow button to toggle Yes or No until Yes is displayed.
- Press Save to reset the displayed records to the factory defaults, or press Back to exit without resetting.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.