Kohler MPAC 1500 — Procedure to Clear a Module Status Conflict
Maintenance · Accessory I/O modules
For the Kohler MPAC 1500, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Do not disconnect modules with the power connected. Connecting or disconnecting modules when the power is connected will damage the ATS controller.
Procedure
- Disconnect power to the transfer switch. Do not disconnect modules with power connected.
- Disconnect the module.
- Close the enclosure door and reconnect power; the display will show Module Status Change.
- Press the button labelled Reset; the display will show Check Module Setup to Clear Fault.
- Uninstall the module through the ATS controller keypad (Section 2.8.2).
- Disconnect power to the ATS and connect the new module.
- Close the door and reconnect power; press Reset to display Reset New Module, then press Reset again.
- Navigate to the Set Auxiliary I/O screen to check the status and settings for the new module.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.