Kohler MPAC 1500 — Control Circuit Isolation Procedure

Maintenance · ATS controller assembly

For the Kohler MPAC 1500, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.
  • There is still power to the controller assembly after the service disconnect is completed. The line side lugs are active at all times.

Procedure

  1. Perform the service disconnect procedure in Section 1.6.1.
  2. Open the enclosure door and move the control circuit isolation switch to the OFF position.
  3. Use a voltmeter to verify that there is no power to the ATS controller assembly before removing the controller.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.