Kohler MPAC 1500 — Bypass and Isolate the Transfer Switch

Installation

For the Kohler MPAC 1500, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.
  • Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergize all power sources before servicing.

Procedure

  1. Bypass the ATS to normal, then rack the ATS out to the isolate position.
  2. Place the generator set master switch in the OFF position or press the OFF/RESET button.
  3. Disconnect power to the battery charger, if equipped.
  4. Disconnect the generator set engine starting battery(ies), negative (--) lead first.
  5. Disconnect power from the transfer switch on both sources, Normal and Emergency.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.