Kohler MPAC 1200 — Time-Based Load Control Setup

Installation · Load control outputs

For the Kohler MPAC 1200, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. Connect each selected load to an output terminal on the main logic board or an I/O module.
  2. Use the Set Inputs/Outputs menu to assign the connected output to load control outputs 1–9.
  3. Navigate to the Set S1 Time Delays or Set S2 Time Delays menu.
  4. In the Set S1 Time Delays menu, select Time as the load control mode.
  5. Enter the number of loads to control (equal to the number of loads connected).
  6. Set Load # Disc N>E pre-transfer time delay in minutes:seconds, up to 60 minutes.
  7. Set Load # Reconn E>N post-transfer time delay in minutes:seconds, up to 60 minutes.
  8. Enter Loads to Add (1 to 9).
  9. For source 2, repeat steps in the Set S2 Time Delays menu.

Specs & values

  • Pre/post-transfer load control time delays up to 60 minutes

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.