Kohler MPAC 1200 — Time-Based Load Control Setup
Installation · Load control outputs
For the Kohler MPAC 1200, from the Kohler service manual.
Browse Kohler generators & specs →
Procedure
- Connect each selected load to an output terminal on the main logic board or an I/O module.
- Use the Set Inputs/Outputs menu to assign the connected output to load control outputs 1–9.
- Navigate to the Set S1 Time Delays or Set S2 Time Delays menu.
- In the Set S1 Time Delays menu, select Time as the load control mode.
- Enter the number of loads to control (equal to the number of loads connected).
- Set Load # Disc N>E pre-transfer time delay in minutes:seconds, up to 60 minutes.
- Set Load # Reconn E>N post-transfer time delay in minutes:seconds, up to 60 minutes.
- Enter Loads to Add (1 to 9).
- For source 2, repeat steps in the Set S2 Time Delays menu.
Specs & values
- Pre/post-transfer load control time delays up to 60 minutes
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.