Kohler MPAC 1200 — SPD Replacement Procedure
Maintenance · Surge protection device (SPD)
For the Kohler MPAC 1200, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Hazardous voltage. Will cause severe injury or death. This equipment must be installed and serviced by qualified electrical personnel.
Procedure
- Disable the generator set: move master switch to OFF, disconnect battery charger power, remove battery negative lead first.
- Disconnect power to the transfer switch: open the normal and emergency source circuit breakers upstream.
- Remove the enclosure’s inner panel, if equipped.
- Open the fuse holder.
- Remove the cartridge by pulling straight out.
- Replace the SPD cartridge with the appropriate service part.
- Close the fuse holder.
- Replace the enclosure’s inner panel, if equipped.
- Reconnect power to the transfer switch by closing the normal and emergency source circuit breakers.
- Check the SPD status indicators.
- Reconnect the generator set engine starting battery, negative lead last.
- Reconnect power to the battery charger.
- Close and lock the ATS enclosure door.
- Move the generator set master switch to the AUTO position.
Specs & values
- Cartridges are keyed for the phases or the neutral; obtain the correct service part for each cartridge
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.