Kohler MPAC 1200 — Procedure to Clear a Module Status Conflict
Testing & diagnosis · Accessory modules
For the Kohler MPAC 1200, from the Kohler service manual.
Browse Kohler generators & specs →
Procedure
- Disconnect power to the transfer switch.
- Disconnect the module.
- Close the enclosure door and reconnect power to the ATS; display shows Module Status Change.
- Press the button labeled Reset; display shows Check Module Setup to Clear Fault.
- Uninstall the module through the ATS controller keypad (Section 1.11.1).
- Disconnect power to the ATS.
- Connect the new module.
- Close the enclosure door and reconnect power; display shows Module Status Change.
- Press Reset to display Reset New Module; press reset from that menu.
- Navigate to the Set Auxiliary I/O menu to check the status and settings for the new module.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.