Kohler MPAC 1200 / MPAC 1500 — Procedure to Clear a Module Status Conflict

Repair & overhaul · Accessory module

For the Kohler MPAC 1200 / MPAC 1500, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Disconnect all power sources before opening the enclosure.

Procedure

  1. Disconnect power to the transfer switch.
  2. Disconnect the module.
  3. Close the enclosure door and reconnect power; the display shows Module Status Change.
  4. Press the button labelled Reset; the display shows Check Module Setup to Clear Fault.
  5. Uninstall the module through the ATS controller keypad.
  6. Disconnect power to the ATS.
  7. Connect the new module.
  8. Close the enclosure door and reconnect power; the display shows Module Status Change.
  9. Press Reset to display Reset New Module, then press Reset again.
  10. Navigate to the Set Auxiliary I/O screen to check the status and settings for the new module.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.