Kohler MPAC 1200 / MPAC 1500 — Millivolt Drop Test Procedure
Maintenance · Main power contacts
For the Kohler MPAC 1200 / MPAC 1500, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Testing live electrical circuits. Have trained and qualified personnel take diagnostic measurements of live circuits.
Procedure
- Apply a balanced load of at least 10% of the switch rating.
- Measure the voltage on each phase of both sources from source lug to load lug.
- Use an ammeter to measure current flow through the circuit.
- Calculate contact resistance using the formula R = V divided by I.
- Compare calculated resistance to the maximum contact resistance table.
- If resistance is 2 times larger or more, disconnect power, check connections and lug torques, and repeat the test; replace contact if still high.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.