Kohler MPAC 1200 / MPAC 1500 — Millivolt Drop Test Procedure

Maintenance · Main power contacts

For the Kohler MPAC 1200 / MPAC 1500, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Testing live electrical circuits. Have trained and qualified personnel take diagnostic measurements of live circuits.

Procedure

  1. Apply a balanced load of at least 10% of the switch rating.
  2. Measure the voltage on each phase of both sources from source lug to load lug.
  3. Use an ammeter to measure current flow through the circuit.
  4. Calculate contact resistance using the formula R = V divided by I.
  5. Compare calculated resistance to the maximum contact resistance table.
  6. If resistance is 2 times larger or more, disconnect power, check connections and lug torques, and repeat the test; replace contact if still high.