Home›Repair guides›Kohler›Controller Application Program / Firmware Update

Kohler MPAC 1200 / MPAC 1500 — Controller Application Program / Firmware Update

Operation · Controller firmware

For the Kohler MPAC 1200 / MPAC 1500, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. On your computer, go to Kohler TechTools.
  2. Click on Software and then ATS Controllers.
  3. Download the latest software version (file MpacDmAppV###.zip).
  4. Save the file onto your laptop computer.
  5. Connect the computer to the ATS controller using a USB cable and start SiteTech.
  6. Select Update Firmware near the top of the screen.
  7. In the Update Firmware dialog box, click Browse, select the firmware zip file, and click Open.
  8. Click the Update Firmware button to load the new firmware onto the controller.
  9. After loading, check system settings, input/output assignments, and time delays.
  10. Run a loaded test to verify correct operation.

Tools required

  • Personal computer with Kohler SiteTech software Amazon
  • USB cable Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.