Kohler MPAC 1200 / MPAC 1500 — Calibration (Voltage/Current)

Adjustments · Controller calibration

For the Kohler MPAC 1200 / MPAC 1500, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Testing live electrical circuits. Have trained and qualified personnel take diagnostic measurements of live circuits.

Procedure

  1. Measure the source voltages as instructed in Section 4.4.3 and record the measured values.
  2. Connect a computer to the MPAC controller and start the SiteTech program.
  3. Click on Parameters and scroll to MPAC Source 1 Calibration or MPAC Source 2 Calibration.
  4. Enter the measured voltage into the corresponding calibration line.
  5. Click on Apply Changes to save the new calibration settings.
  6. For current calibration, enter the measured current (amps) into the corresponding Calibration Factor Load Current L1, L2, or L3 setting.

Tools required

  • Personal computer with Kohler SiteTech software Amazon
  • Digital voltmeter Amazon
  • Clamp-on current sensing meter (current calibration) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.