Kohler MPAC 1200 / MPAC 1500 — Automatic Operation Test Procedure
Operation · Transfer switch / controller
For the Kohler MPAC 1200 / MPAC 1500, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Hazardous voltage. Only authorized personnel should open the enclosure.
- Close and lock the enclosure door before starting the test procedure.
Procedure
- Check controller LED indicators; verify Position N and Source N Available indicators are lit.
- Verify the generator set master switch is in the AUTO position.
- From the main screen, press the Test button; enter test password and press OK.
- Press the down arrow button to display Type of Test Loaded.
- Press the Start button.
- Verify that the generator set starts and the Source E Available LED lights.
- Verify the switch transfers the load to Source E.
- Press the End Test button.
- Verify the switch transfers the load back to Source N.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.