Home›Repair guides›Kohler›Module Uninstall Procedure

Kohler MPAC 1200 — Module Uninstall Procedure

Maintenance · Accessory I/O modules

For the Kohler MPAC 1200, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. Press Main to return to the main menu.
  2. Press Set to enter setup mode.
  3. Enter the setup password.
  4. Press the down arrow to step to the Set Inputs/Outputs menu.
  5. Navigate to the Set Auxiliary I/O menu.
  6. Press the right arrow to see module 1 status; step down until the menu shows Status: Lost.
  7. Press the right arrow to the Uninstall Module menu; verify Uninstall Module Yes.
  8. When Yes is displayed, press Save to uninstall the module.
  9. Repeat the uninstall procedure for additional modules, if necessary.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.