Kohler MPAC 1200 — Manual Transfer Procedure

Operation · Supervised transfer control switch (AUTO/MANUAL/TRANSFER)

For the Kohler MPAC 1200, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • The switch will not cause a transfer unless an event has initiated a transfer sequence.

Procedure

  1. An event occurs such as loss of the connected source, the start of a loaded exercise, or an operator starts a loaded test.
  2. The ATS executes time delays and signals the generator set engine to start.
  3. MANUAL TRANSFER is displayed and the Not-in-Auto LED flashes.
  4. Turn the keyswitch to the TRANSFER position and release.
  5. The load is transferred to the standby source, if available.
  6. When the preferred source returns or the exercise or test ends, turn the keyswitch to TRANSFER and release to transfer back.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.