Kohler — MCP 3000 Power-Up and Initial Checks

Installation

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Place all Decision-Maker 6000 controllers in OFF mode.
  2. Verify 24 VDC between TB2-1 and TB2-2.
  3. Install fuses F1 and F2.
  4. Verify the RS-485 communication daisy chain is connected.
  5. Verify the PLC powers up and enters Run Mode.
  6. Verify the HMI powers up and displays the main screen.
  7. Log in to the HMI with username Setup (factory default password Setup).
  8. Set the number of generators in the system.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.