Kohler — Mapping Address Table Procedure (Master Device Only, Parameter Set 5)
Installation · Modbus/Ethernet Converter (RSA Master)
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Before you start
- Do not copy the Network/IP settings shown in the figures. Consult your network administrator.
Procedure
- At the Telnet Configuration command line, type 5 to enter parameter set 5.
- For Close Idle TCP sockets type 10; for Redundant entry retries type 0.
- At A)dd, D)elete, E) select function, type A to add a Modbus address and IP address.
- Type the Modbus address for the controller. RSA 1000: type 1 for both Modbus addr from and to.
- For RSA II or RSA III, type the controller Modbus address for both entries (e.g. 17).
- At Slave IP address, enter the IP address for the controller's Modbus/Ethernet converter.
- To add RSA slaves through another converter, return to step 3; RSA 1000 slaves use 247; RSA II/III slaves use their own address.
- At A)dd, D)elete, E) select function, type E to exit parameter set 5.
- At D)efault settings, S)ave, Q)uit without save, type S to save the settings.
Specs & values
- An RSA 1000 master can communicate with one generator set controller and multiple RSA 1000 slaves
- A controller communicating with the RSA 1000 must have Modbus address 1
- RSA 1000 slaves have Modbus address 247
- RSA II or RSA III controller and slave addresses can be any number from 1 to 247
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.