Kohler — Manual Operation Procedure 2 (100-200 amp 3-phase, and 400 amp 3-phase)

Operation · Contactor / transfer mechanism

From a Kohler service manual covering: RXT-JFNC-0100A, RXT-JFNC-0200A, RXT-JFNC-0400. Check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Never use the maintenance handle to transfer the load with the power connected. Disconnect both power sources before manually operating the switch.

Procedure

  1. If equipped with a maintenance handle, remove it from its storage location inside the enclosure
  2. Insert the maintenance handle or a tool such as a screwdriver into the hole in the shaft on the left side of the operator
  3. Move the maintenance handle or tool up or down to manually operate the transfer switch; it should operate smoothly without binding
  4. Return the transfer switch to the Normal position
  5. Remove the maintenance handle and return it to the storage location