Kohler — Manual Operation Procedure 1 (100-200 amp switches, and 400 amp single-phase/208-240 Volt)

Operation · Contactor / transfer mechanism

From a Kohler service manual covering: RXT-JFNC-0100A, RXT-JFNC-0200A, RXT-JFNC-0400. Check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Never manually operate the transfer switch when the power is connected. Disconnect both power sources before manually operating the switch.

Procedure

  1. 100-200 amp switches have an attached handle (Figure 2-4); 400 amp switches: slide the detachable handle or a wrench over the shaft (Figure 2-5)
  2. Move the handle up to place the transfer switch in the Normal Source position or down to place the contactor in the Emergency Source position
  3. 400 amp switches: remove the detachable handle or wrench