Home›Repair guides›Kohler›Manual Operation

Kohler — Manual Operation

Operation · Automatic transfer mechanism

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Transfer cannot occur unless the source circuit breaker is in the ON position.

Procedure

  1. Use the controller's Test button to try to initiate transfer first.
  2. Verify neither source breaker is tripped and that the selected source breaker is ON.
  3. Use a 7/16 in. socket and driver to move the hex drive to the desired power source.
  4. Rotate the hex drive fully counterclockwise to transfer from Utility to Generator.
  5. Rotate the hex drive fully clockwise to transfer from Generator to Utility.
  6. Do not exceed 1.3 Nm (100 in. lb.) when manually operating the mechanism.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 1.3 Nm (100 in. lb.) maximum

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.