Kohler — Manual Operation
Operation · Automatic transfer mechanism
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Before you start
- Transfer cannot occur unless the source circuit breaker is in the ON position.
Procedure
- Use the controller's Test button to try to initiate transfer first.
- Verify neither source breaker is tripped and that the selected source breaker is ON.
- Use a 7/16 in. socket and driver to move the hex drive to the desired power source.
- Rotate the hex drive fully counterclockwise to transfer from Utility to Generator.
- Rotate the hex drive fully clockwise to transfer from Generator to Utility.
- Do not exceed 1.3 Nm (100 in. lb.) when manually operating the mechanism.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 1.3 Nm (100 in. lb.) maximum
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.