Kohler M340 — Voltage Sensing Calibration (Index 12)

Adjustments · M340 controller

For the Kohler M340, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Unit starts without notice

Procedure

  1. De-energize or disconnect the emergency source; open the emergency breaker.
  2. Enter index 12 for Calibration.
  3. Press YES at E-AUTO-ZERO to zero the emergency voltmeter.
  4. Connect a 1%-accurate or better voltmeter to the lugs.
  5. Close the emergency breaker or start the generator set.
  6. Enter the voltmeter reading for each phase.
  7. Open normal-source breaker, place switch in emergency position, zero and calibrate normal voltmeter.

Tools required

  • 1%-accurate or better voltmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Meter calibration is factory set
  • Calibration normally only needed if system voltage changes or control replaced

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.