Kohler M340 — To Reconnect The P1 Plug
Maintenance · P1 in-line disconnect plug
For the Kohler M340, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Connecting the transfer switch in-line disconnect plugs (P1) together when the generator controller's master switch is in the AUTO position causes the generator set to IMMEDIATELY start and run.
Procedure
- Engage the in-line disconnect plug by grasping the connectors and pressing them together.
- If the transfer switch is in the normal position, place the generator set start switch in the AUTO position. Then close the emergency-source circuit breaker.
- If the transfer switch is in the emergency position, close the normal-source circuit breaker.
- The load will automatically retransfer to the normal source, if available, after a time delay. For immediate retransfer, open and then reclose the emergency-source circuit breaker.
- Place the generator set start switch in the AUTO position.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.