Home›Repair guides›Kohler›Set Normal Source Voltage and Frequency Set Points (Index 6)

Kohler M340 — Set Normal Source Voltage and Frequency Set Points (Index 6)

Adjustments · M340 controller

For the Kohler M340, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. Place programming mode switch in LOCAL position.
  2. Enter index 6 for Normal System.
  3. Set NORM VOLTS to match system voltage.
  4. Set NORM HERTZ to match system frequency.
  5. Select one-phase or 3-phase sensing.
  6. Set over/under voltage and frequency pickup and dropout percentages.
  7. Press STORE SETPOINTS.

Specs & values

  • Settings may only be changed as a percentage, not voltage or frequency
  • Dropout settings must be at least 2% different than pickup settings

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.