Kohler M340 — Load Shed Setup (Index 9)
Operation · M340 controller
For the Kohler M340, from the Kohler service manual.
Browse Kohler generators & specs →
Procedure
- Load-shed circuit board must be installed.
- Enter index 9 for Load Shed in minutes:seconds.
- Set NORM-EMER before, after, sequence times and loads return number.
- Set EMER-NORM before, after, sequence times and loads return number.
Specs & values
- Up to 9 loads may be controlled by sequence
- If sequence is 00:00 all relays energize simultaneously
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.