Home›Repair guides›Kohler›Calibrate The Logic Board Emergency Source Voltage

Kohler M340 — Calibrate The Logic Board Emergency Source Voltage

Adjustments

For the Kohler M340, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Never auto-zero the source unless it is zero volts.

Procedure

  1. Choose single-phase or three-phase emergency sensing in Menu Index 7 (three-phase requires option DD-05-K).
  2. Using the menu in Index 12, press YES at the E-AUTO-ZERO? message. Do not press ENTER yet.
  3. Disconnect the emergency power source; press the ENTER key.
  4. Observe the ENTRY ACCEPTED message on the LCD.
  5. When the LCD again reads E-AUTO-ZERO?, reconnect the emergency power source.
  6. Measure emergency voltage (E-VOLT VAC or E-PH A-B, B-C, A-C VAC) and enter the measured values; press ENTER.
  7. Press the RESET MENU key and then the ENTER key to store the setpoints.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →