Kohler M340 — Calibrate Logic Board Normal Single-Phase Source

Adjustments · Logic board normal source voltage

For the Kohler M340, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Never auto-zero the source unless it is zero volts.

Procedure

  1. Using the menu in Index 12, arrow down to N-AUTO-ZERO?. Press the YES key and the ENTER key.
  2. Observe the ENTRY ACCEPTED message on the LCD.
  3. When the LCD again reads N-AUTO-ZERO?, restore the normal power source.
  4. Press the MENU Arrow Down key so the LCD reads N-VOLT VAC. Value should be between 60% and 80% of system voltage.
  5. Measure normal system voltage at TB-AC1-NA to TB-AC1-NC. Enter the measured value at N-VOLT VAC; press ENTER.
  6. Press the RESET MENU key and then the ENTER key to store the set points.