Adjustments · JP1 shunt-jumper socket on main logic board
For the Kohler M340, from the Kohler service manual.
Browse Kohler generators & specs →
Before you start
- Do not remove the MANUAL OVERRIDE jumper.
Procedure
- Add/remove shunt-jumpers across the terminals next to the option name on JP1. Do not remove the MANUAL OVERRIDE jumper.
- Go to Index 20 and press Menu Down; look for OPTIONS LOCK? NO. Lock the options by answering YES then ENTER if desired.
- Power down the controller by disconnecting the inline disconnect plug P1.
- Wait a minimum of 1 minute then reconnect plug P1 to power up the controller.
- Check Index 11; YES should appear only after the Index 11 listing of options with installed shunt jumpers.