Kohler — Load Management Configuration
Operation · MCP 3000 Load Management
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Configure the priority for each load control relay (add/shed contact).
- Configure the expected load of each load control relay.
- Configure generator online add delay.
- Configure delay for GOL add before kW capacity add.
- Configure the kW capacity time between adds.
- Configure maximum percentage to auto load generators.
- Configure under frequency load shed priority, setpoint, and time delay.
- Configure kW overload setpoint and time between sheds.
Specs & values
- Priority 2 through 8 acceptable
- Priority 1 is not shed
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.