Kohler K361 — Choke Unit Replacement and Adjustment

Adjustments · Automatic choke (Thermo-Electric)

For the Kohler K361, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Always remove spark plug lead before working on or near carburetor or choke area.

Procedure

  1. Position the choke unit on the two mounting screws so that it is slightly loose.
  2. Hold the choke plate in the wide open position.
  3. Rotate choke unit clockwise (viewed from choke side) until it can no longer be rotated.
  4. Hold choke unit in position and tighten the two mounting screws.
  5. Check choke function by removing spark plug lead and cranking; choke valve should close a minimum of 45 degrees at about 75 degrees F.

Specs & values

  • Choke valve closed 45 degrees minimum at about 75 degrees F

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.