  1. Connect the interface module to a Kohler generator set equipped with the RDC2 or DC2 controller via the field-connection terminal block
  2. Use 20 AWG Belden #9402, 8723, or equivalent shielded twisted-pair cable to connect P10-1 through P10-4 to generator set terminal block connections A, B, PWR, and COM
  3. Maximum cable length is 61 meters (200 ft.); alternatively use 12-14 AWG wire for PWR and COM only, up to 152 m (500 ft.) with one RXT switch and no accessory modules
  4. Leave one end of each cable shield disconnected; if accessory modules are connected in series, connect the cable shields as shown and refer to the generator set installation manual
  5. Connections 3 and 4 on the generator set terminal block are NOT USED with the Model RXT ATS