Procedure
- If the load center is not predrilled, drill mounting holes using a number 28 (0.140 in.) drill bit.
- Place the load shed module in the load center and loosely secure it with the two captive screws.
- Slide the spade connector of the shield wire between the module mounting screw and the module housing.
- Connect cable GM54832 (Type 1) or GM48761 (Type 3R) to the bottom connector and to terminal TB1.
- Connect cable GM54830 to the top terminal and to terminal J3 on the transfer mechanism.
- If installing two modules in a Type 1 load center, install jumper cable GM54831 between them.
- Set the module selector switches to two different settings.