Kohler — Installing Fuse Holders
Installation
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Before you start
- Hazard of electric shock, explosion, or arc flash. Will cause severe injury or death.
Procedure
- Pull the fuse clips and fuses out of the fuse holders.
- Bend the insulating covers to fit around the fuse holders.
- With a size 2 Phillips driver, insert two mounting screws into the bottom of each fuse holder.
- Install the two fuse holders (GM48746); secure each with two screws (GM48748).
- Torque screws to 3.4 Nm (30 in. lb.).
- Apply the fuse replacement label GM40861.
- Route the leads between the fuse holder and the wireway brackets.
Tools required
- size 2 Phillips driver Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 3.4 Nm (30 in. lb.)
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.