Kohler — Installation Guidelines (siting, clearances, pad)

Installation · Genset installation

From a Kohler service manual covering: 48RCLB, 60RCLA, 60RCLB. Check it applies to your exact model before use.

Applies to: Kohler 48RCLB, Kohler 60RCLA, Kohler 60RCLB

Procedure

  1. Exhaust is aimed away from or parallel to the structure.
  2. Exhaust is not directed at play areas, patios or other areas where people congregate.
  3. Nearest window, vent, door or similar structure opening is at least 5 feet from the exhaust end of the set.
  4. Set has proper offset from structure.
  5. Windows and doors on adjacent walls are closed.
  6. Furnace and other similar intakes are at least 10 feet from exhaust end of set.
  7. 4" thick concrete pad extending 6" beyond genset on all sides.
  8. Weed barrier and gravel bed to extend 4 ft. from exhaust outlet; no plants, shrubs or other combustibles allowed in gravel area.
  9. Sensitive plants, patio furniture, etc. are at least 8 feet from exhaust end of set.
  10. Refer to owners manual for other installation constraints.

Specs & values

  • NFPA 37 states distance should be at least 5 feet from a combustible material
  • Minimum distance of 3 feet near non-combustible material to ensure proper generator cooling

Full service-parts list: Kohler 48RCLB →, Kohler 60RCLA →, Kohler 60RCLB →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.