Kohler — Installation Guidelines (siting, clearances, pad)
Installation · Genset installation
From a Kohler service manual covering: 48RCLB, 60RCLA, 60RCLB. Check it applies to your exact model before use.
Applies to: Kohler 48RCLB, Kohler 60RCLA, Kohler 60RCLB
Procedure
- Exhaust is aimed away from or parallel to the structure.
- Exhaust is not directed at play areas, patios or other areas where people congregate.
- Nearest window, vent, door or similar structure opening is at least 5 feet from the exhaust end of the set.
- Set has proper offset from structure.
- Windows and doors on adjacent walls are closed.
- Furnace and other similar intakes are at least 10 feet from exhaust end of set.
- 4" thick concrete pad extending 6" beyond genset on all sides.
- Weed barrier and gravel bed to extend 4 ft. from exhaust outlet; no plants, shrubs or other combustibles allowed in gravel area.
- Sensitive plants, patio furniture, etc. are at least 8 feet from exhaust end of set.
- Refer to owners manual for other installation constraints.
Specs & values
- NFPA 37 states distance should be at least 5 feet from a combustible material
- Minimum distance of 3 feet near non-combustible material to ensure proper generator cooling
Full service-parts list: Kohler 48RCLB →, Kohler 60RCLA →, Kohler 60RCLB →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.