Kohler GM22703-KP1 / GM22703-KP3 — Restore the generator set and transfer switch to service
Installation · Transfer switch / generator set
For the Kohler GM22703-KP1 / GM22703-KP3, from the Kohler service manual.
Browse Kohler generators & specs →
Procedure
- Close and secure the transfer switch enclosure.
- Close and secure the transfer switch security cover.
- Check that all generator set master switches are in the OFF position.
- Reconnect the generator set engine starting battery(ies), negative (--) leads last.
- Reconnect power to the battery charger, if equipped.
- Reconnect all power sources to the transfer switches and power monitors.
- Reconnect power to all devices in the system.
- Place all generator set master switches in the AUTO position.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.