Kohler — Generator Management Configuration

Operation · MCP 3000 Generator Management

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Decision-Maker 6000 controller must be in remote programming mode.

Procedure

  1. Configure the generator start percentage and time delay.
  2. Configure the generator stop percentage and time delay.
  3. Configure the generator overload percentage and time delay.
  4. Configure the order selection method (manual or runtime).
  5. Configure minimum number of generators online (N or N+1).
  6. Configure the stable timer.
  7. Set generator management to Auto.

Specs & values

  • Good start percentage range is 65% to 90%
  • Good stop percentage range is 45% to 75%
  • Good overload percentage range is 85% to 100%

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.