Kohler — Generator Management Configuration
Operation · MCP 3000 Generator Management
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Before you start
- Decision-Maker 6000 controller must be in remote programming mode.
Procedure
- Configure the generator start percentage and time delay.
- Configure the generator stop percentage and time delay.
- Configure the generator overload percentage and time delay.
- Configure the order selection method (manual or runtime).
- Configure minimum number of generators online (N or N+1).
- Configure the stable timer.
- Set generator management to Auto.
Specs & values
- Good start percentage range is 65% to 90%
- Good stop percentage range is 45% to 75%
- Good overload percentage range is 85% to 100%
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.