Kohler — FR Activator Replacement (Standard)

Repair & overhaul

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • HIGH VOLTAGE! Do not reverse FR activator leads E and C. Ceiling voltage will result causing equipment damage and possible personal injury.
  • FR ACTIVATOR DAMAGE! Overtightening FR activator screws can cause activator failure. Do not exceed maximum torque settings.

Procedure

  1. See “End Bracket Removal and Replacement.”
  2. Observe label markings on the FR activator. Leads F3 and F4 are generator field leads; leads A1 and A2 are exciter armature leads; lead E (black) is emitter; lead C (red) is collector.
  3. Apply a thin coating of thermal compound to back of activator before mounting.
  4. Using new washers install washers so the convex side is against socket cap screwhead.
  5. Tighten FR activator mounting screws to 20-25 in. lbs. (2.3-2.8 Nm) or only as necessary to compress washers.
  6. Connect leads to FR activator and tighten A and F terminal screws to 20-25 in. lbs. (2.3-2.8 Nm).
  7. Secure leads with tie cable.