Kohler Ford LSG-423 — Initial Ignition Timing Adjustment

Adjustments · Ignition System

For the Kohler Ford LSG-423, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Do not puncture the secondary wires with a probe when setting ignition timing

Procedure

  1. Clean and mark the specified timing mark with chalk or white paint
  2. Disconnect the vacuum line and plug the disconnected vacuum line
  3. Connect a timing light to the No. 1 cylinder spark plug wire; connect a tachometer
  4. Start engine and reduce idle speed to 600 rpm to be sure the centrifugal advance is not operating
  5. Adjust the initial ignition timing to specifications by rotating the distributor
  6. Check the centrifugal advance by accelerating to approximately 2000 rpm
  7. Unplug the vacuum line, connect it, and accelerate to approximately 2000 rpm; advance should begin sooner and advance farther
  8. If the vacuum advance is not functioning properly, remove the distributor and check it on a distributor tester; replace the diaphragm unit if out of calibration

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Initial spark advance 10° BTDC
  • Idle speed 600 rpm

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.