For these Kohler models: 10/15RMOY, 15/17.5ROY, 15RMY, 22.5-47.5ROZ, 22.5/32.5RZ.

Applies to: Kohler 15Rmy, Kohler 22 5 47 5Roz

Before you start

  • lobe at 0.020" (0.508 mm) (Figure 4-17). CAUTION

Procedure

  1. 10. To remove the rotor loosen the thru bolt 2-3 turns and
  2. break the rotor loose from taper by striking the bolt
  3. head with a heavy lead mallet. \f after striking bolt
  4. head the rotor can be rocked slightly back and forth in
  5. 1. Vibro-Mount place, remove thru bolt and pull rotor away from en-
  6. 2. Ground Strap gine. If rotor is not loose, repeat procedure. The gen-
  7. Figure 4-9. Stator Mounting erator fan will be removed with rotor (Figure 4-14).
  8. 1. Brush Leads
  9. 2. Brush Holder
  10. 3. Retainer Wire
  11. Figure 4-11. Lifting Brushes
  12. Figure 4-12. End Bracket Removal
  13. 1. End Bracket
  14. 2. Tolerance Ring
  15. Figure 4-15. Stator Position
  16. Figure 4-16. Tolerance Ring
  17. Use a feeler gauge to set air gap between sensor and
  18. lobe at 0.020" (0.508 mm) (Figure 4-17). CAUTION
  19. If brush retainer wire is not removed, voltage
  20. regulator will be damaged when generator is

Tools required

  • Use a feeler gauge to set air gap between sensor and

Source: manual:R Series Service TP5074.PDF. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.