Procedure

  1. Press and hold the test button for 2 seconds.
  2. After the standby-to-normal time delay, the ATS transfers the load back to the normal source.
  3. The load control contact closes.
  4. The optional load shed circuit breakers close.
  5. After the engine cooldown time delay, the generator set stops.
  6. The Generator Available LED stops flashing when the standby source is no longer available.