Kohler — EBSM/BOB Connection and Voltage Setting

Installation · external battery supply module (EBSM/BOB)

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Use #14-28 AWG wire to connect one or two batteries to terminal block TB13, positive (+) and negative (--) as marked.
  2. Set voltage selector switch SW11-1 to 12 or 24 VDC. Switch SW11-2 is not used.
  3. Note: If battery connections are reversed, red LED1 or LED2 will light.
  4. Note: The EBSM/BOB has no address switches but must be the last board on the bus.

Specs & values

  • EBSM/BOB produces 2 amps at 12 VDC with 9--36 VDC input

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.