Kohler — Decision-Maker 6000 Controller Connection Procedure

Installation · Decision-Maker 6000 Generator Set Controller

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.

Procedure

  1. Press the OFF button on the controller.
  2. Disconnect the power to the battery charger, if equipped.
  3. Disconnect the generator set engine starting battery(ies), negative (--) lead first.
  4. Turn off and disconnect the power to all devices in the system.
  5. Open the enclosure and locate the connection ports as shown in Figure 7-1 and Figure 7-3.
  6. For RS-232 connections, use connector P18. For RS-485 connections, use Modbus RS-485 connector P19 or P20.
  7. Close the controller enclosure.
  8. Verify that the controller is OFF.
  9. Reconnect the generator set engine starting battery, negative (--) lead last.
  10. Reconnect power to the battery charger, if equipped.
  11. Proceed to Section 13 to configure the controller's communication parameters.

Specs & values

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.