Home›Repair guides›Kohler›Decision-Maker 3000 Connection Procedure

Kohler — Decision-Maker 3000 Connection Procedure

Installation · Decision-Maker 3000 Generator Set Controller

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.

Procedure

  1. Press the OFF button on the controller.
  2. Disconnect the power to the battery charger, if equipped.
  3. Disconnect the generator set engine starting battery(ies), negative (--) lead first.
  4. Turn off and disconnect the power to all devices in the system.
  5. Connect to communication port P21 as shown in Figure 8-1.
  6. Verify that the controller is OFF.
  7. Reconnect the generator set engine starting battery, negative (--) lead last.
  8. Reconnect power to the battery charger, if equipped.
  9. Proceed to Section 13. Use Kohler SiteTech software and a PC connected to the controller's USB port to configure communication parameters.

Tools required

  • Kohler SiteTech software Amazon
  • Personal computer with USB port Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Controller firmware version 2.08 or higher is required for Modbus communication

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.