Kohler — Current-Based Load Control Setup Procedure

Installation

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Connect each selected load to an output terminal on the main logic board or an I/O module.
  2. Assign the connected output to a load control output 1-9 in the Set Inputs/Outputs menu.
  3. In the Set S1 or Set S2 Time Delays menu, select Current as the load control mode.
  4. Enter the number of loads to control.
  5. Set the Load Disc N>E (or E>N) time delay before transfer.
  6. Set the Load Add Source1 (or Source2) time delay and priority.
  7. Set the Load Remove Src1 (or Src2) time delay and priority.
  8. Enable load control for the selected load; set Hi and Lo current levels.

Specs & values

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.