Kohler — Current-Based Load Control Setup Procedure
Installation
From a Kohler service manual — check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Connect each selected load to an output terminal on the main logic board or an I/O module.
- Assign the connected output to a load control output 1-9 in the Set Inputs/Outputs menu.
- In the Set S1 or Set S2 Time Delays menu, select Current as the load control mode.
- Enter the number of loads to control.
- Set the Load Disc N>E (or E>N) time delay before transfer.
- Set the Load Add Source1 (or Source2) time delay and priority.
- Set the Load Remove Src1 (or Src2) time delay and priority.
- Enable load control for the selected load; set Hi and Lo current levels.
Specs & values
- High current level range 0-4000 Amazon eBay FridayParts $239.27 Amps.
- Low current level range 0-4000 Amazon eBay FridayParts $239.27 Amps.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.