Kohler — Contactor Removal

Repair & overhaul

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening enclosure.

Procedure

  1. Disconnect both the normal and emergency power sources.
  2. Open the enclosure door of the ATS.
  3. Disconnect the normal and emergency power sources and load connections from the contactor terminals.
  4. Disconnect P1 of the contactor assembly harness from P1 of the logic control harness.
  5. Remove the screws and flat washers. Lift the switch panel out of the enclosure.
  6. Place the contactor assembly on a work bench.
  7. Remove the tie bars between the load connection lugs of the two contactors.
  8. Disconnect wiring harness from auxiliary switch and contactor coil.
  9. Remove screws and separate the contactor from the contactor assembly panel.
  10. Remove the mechanical interlock from the contactor.
  11. Remove the auxiliary switch from the contactor.
  12. On 25-80 ampere mechanically held contactors, remove the mechanical latch.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.