Kohler — Contactor Installation

Repair & overhaul

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Can cause severe injury or death. Disconnect power sources before servicing.

Procedure

  1. On 25-80 ampere mechanically held contactors, install the mechanical latch.
  2. Install the auxiliary switch on the contactor.
  3. Install the mechanical interlock on the contactor assembly.
  4. Place the contactor assembly onto the switch plate and mate the mechanical interlocks. Install and tighten the screws.
  5. Reconnect the contactor's auxiliary switch and coil to the main harness assembly.
  6. Reinstall the tie bars between the load connectors of the two contactor assemblies.
  7. Place the switch panel back into the enclosure. Install the screws and flat washers.
  8. Reconnect P1 of the switching device panel harness to P1 of the logic control and interface panel harness.
  9. Reconnect the power source and load connections to the contactor terminals.
  10. Shut the enclosure door.
  11. Return the ATS to normal operation.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.